ABB - RCCB 2P Type A - 40A

Save Rs 400.00

Price:
Sale priceRs 1,800.00 Regular priceRs 2,200.00

Description

F202 A-40/0.03 AP-R Residual Current Circuit Breaker Type A -40a

The RCCBs F200 series assures protection to people and installations against fault current to earth. A large offer for standard instantaneous and selective AC and A types is completed with some configurations for special applications. This product provides the best compromise between safety and continuity in the service, thanks to the resistance to unwanted trippings.

 

Technical

  • Standards: IEC/EN 61008, UL 1053
  • Type of Residual Current: A type
  • Rated Voltage (Ur): 230 V
  • Rated Operational Voltage: 230 V
  • Rated Insulation Voltage (Ui): 500 V
  • Rated Impulse Withstand Voltage (Uimp): 4 kV
  • Input Voltage Type: AC
  • Rated Current (In): 40 A
  • Rated Residual Current: 30 mA
  • Rated Conditional Short-Circuit Current (Inc): 10 kA
  • Rated Service Short-Circuit Breaking Capacity (Ics): 1 kA
  • Maximum Surge Current: 3 kA
  • Leakage Current Type: A
  • Rated Frequency (f): 50 … 60 Hz
  • Power Loss: at Rated Operating Conditions per Pole 2.4 W
  • Power Supply Connection: Arbitrary
  • Electrical Endurance: 10000 cycle
  • Number of Poles: 2
  • Operating Characteristic: Instantaneous (APR High Immunity)
  • Mounting Type: DIN rail
  • Options Provided: None
  • Accessories Available: Yes
  • Connecting Capacity:
    Busbar 10 mm²
    Rigid 25 ... 25 mm²
    Flexible 25 ... 25 mm²
  • Rated Cross-Section:
    4 - Multi-Wired 0...25 mm²
    1 - Solid-Core 25...25 mm²

Environmental

  • Ambient Temperature: -25...55 °C
  • Ambient Air Temperature: Operation -25...55 °C
  • Degree of Protection: IP2X
  • Pollution Degree: 2
  • Resistance to Vibrations acc. to IEC 60068-2-6: 0.1 mm or 1 g - 20 cycles at 5…150…5 Hz
  • Resistance to Shock acc. to IEC 60068-2-27: 25g 2 shocks 13 ms
  • RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
  • Environmental Information: Refer to RoHS

Technical UL/CSA

  • Maximum Operating Voltage UL/CSA: 277 V AC
  • Short-Circuit Current Rating (SCCR): 30 mA

Dimensions

  • Width in Number of Modular Spacings: 2
  • Product Net Width: 0.035 m
  • Product Net Height: 0.085 m
  • Product Net Depth / Length: 0.069 m
  • Product Net Weight: 0.200 kg
  • Built-In Depth (t2): 69 mm

 